ZR-YJV22交联高压电力电缆35KV

发布时间:2024-02-15
本产品按gb12706《额定电压35v及以下铜芯、滤芯塑料绝缘电缆》标准生产,同时还可根据用户需要按电工委员会推荐标准iec、英国标准、德国标准及美国标准生产。
the product is manufactured according to the standard of《gb12706 or iec、bs、din and icea upon request.
适用范围applications
本产品适用于工频额定电压3.6/6kv~26/35kv输配电线路作配送电能子用。
the product is suitable for use in power transmission and distribution lines with rated power frequency voltage 3.6/6kv~26/35kv.
使用特性operating characteristics
· 工频额定电压u0/u为3.6/6kv~26/35kv。
rated power-frepuency voltage u0/u: 3.6/6kv~26/35kv.
· 电缆导体的许工作温度:90℃。
max.admissible operating temperature of 温度不超过2500c。
max. short-circurt temperature of conductor shall not exceed 2500c.
(5s maximum duration)
· 电缆敷设时环境温度应不低于00c。
the ambient temperature under installation should not below 00c.
· 电缆弯曲半径:三芯电缆不小于电缆外径15倍;单芯电缆不小于电缆外径20倍。
the bending radius of a single-core cable should not less than 20 times of the cable diameter.
the bending radius of a single-core cable should not less than 15 times of the cable diameter.
电缆额定电压的选择 voltage designation
· 电缆的额定电压应适合于电缆系统的运行状况,用u0/u(um)kv表示。
u0-电缆设计用的导体对地或金属屏蔽之间的额定工频电压;
u-电缆设计用的导体间的额定工频电压;
um-设备可承受的“ 系统电压”的大值。
the rated voltage of the cable for a given applixation shall be suitable for the operating conditions
in the system in which the cable is used,and is expressed in the form of u0/u(um)kv
where:
u0-the rated power-frequency voltage between conductors and earth metallic screen ,for which the cable designed;
u - the rated power-frequency voltage between conductos, for which the cable designed;
um- the maximum value of the“highest system voltage”for which the equipment may beused.